基于FHI-FSM的地铁人员火灾风险评估
Personnel Fire Risk Assessment in Subway Systems Using FHI-FSM
投稿时间:2025-09-01  修订日期:2026-09-23
  查看/发表评论  下载PDF阅读器
DOI:
基金项目:
作者单位邮编
张国会* 张国会 017000
中文关键词:  地铁火灾  FDS模拟  烟气运移规律  FHI-FSM火灾风险模型  状态转移概率
英文关键词:Subway fire  FDS simulation  Smoke movement law  FHI-FSM fire risk model  State transition probability
摘要点击次数: 6
全文下载次数: 0
中文摘要:
      地铁地下空间封闭性强、连通度高,火灾烟气扩散快且易造成群死群伤事故,现有评估方法难以同时实现火灾风险的动态量化、时序演化追踪与空间异质性识别。本文构建了A型6编组列车+岛式站台的全尺寸火灾动力学(FDS)数值模型,设置第2、4、6节车厢及站台配电箱4种典型火灾场景,系统分析了烟气温度、可见度与CO浓度的时空演化特征;提出融合火灾风险指数(FHI)与有限状态机(FSM)的耦合评估方法,引入主导因子动态加权与自适应滑动平均机制优化FHI计算,通过状态转移概率矩阵量化不同起火点的火灾风险演化规律。结果表明,地铁火灾烟气呈现“水平推进-末端滞留”的扩散规律,火灾发生后180-240s为关键环境参数临界恶化时间窗;不同起火点风险演化存在显著异质性,车厢火灾风险沿车头向车尾递减,配电箱火灾风险具有极强的不可逆性与状态固化特征,在本文设定的固定通风、未启用机械排烟的最不利基准工况下,各场景风险均未越过预警等级、未发生跨级跃升。该方法无需依赖稀缺的历史事故样本,可实现火灾风险的结构化量化与动态预警,为地铁站台排烟系统布局、火灾智能监测系统升级提供定量依据。
英文摘要:
      Underground subway spaces are characterized by strong enclosure and high connectivity, where fire smoke spreads rapidly and can easily cause mass casualties. Existing assessment methods struggle to simultaneously achieve dynamic quantification, temporal evolution tracking, and spatial heterogeneity identification of fire risk. In this study, a full-scale Fire Dynamics Simulator (FDS) numerical model of an A-type 6-car train and an island platform was established, and four typical fire scenarios—fires in the 2nd, 4th, and 6th carriages and a platform distribution box fire—were set up to systematically analyze the spatiotemporal evolution characteristics of smoke temperature, visibility, and CO concentration. A coupled assessment method integrating the Fire Hazard Index (FHI) and the Finite State Machine (FSM) was proposed; the FHI calculation was optimized by introducing a dominant-factor dynamic weighting mechanism and an adaptive moving average method, and the fire risk evolution patterns at different ignition points were quantified through state transition probability matrices. The results show that subway fire smoke follows a "horizontal progression–terminal stagnation" diffusion pattern, and 180–240 s after ignition is the critical time window for the deterioration of environmental parameters. Significant heterogeneity exists in risk evolution at different ignition points: carriage fire risk decreases from the head to the tail of the train, while the distribution box fire risk exhibits strong irreversibility and state solidification. Under the most unfavorable baseline condition of fixed ventilation without mechanical smoke extraction set in this study, the risk in all scenarios remained below the warning level with no cross-level jump. This method does not rely on scarce historical accident samples and can realize structured quantification and dynamic early warning of fire risk, providing a quantitative basis for the layout of subway platform smoke exhaust systems and the upgrading of intelligent fire monitoring systems.
关闭