贫氧环境电弧作用下变压器绝缘油产气及燃爆特性研究
Gas Generation and Explosion Characteristics of Transformer Insulating Oil under Arc Discharge in Oxygen-Deficient Environments
投稿时间:2025-12-01  修订日期:2026-03-09
  查看/发表评论  下载PDF阅读器
DOI:
基金项目:深圳供电局有限公司受限空间下变压器油火灾动力学行为及分级预警技术研究科技项目(编号:090000KC24070050)
作者单位邮编
张晶焯 深圳供电局有限公司 518002
郑俊杰 中国科学技术大学火灾安全全国重点实验室 
楚少华 深圳供电局有限公司 
林海 深圳供电局有限公司 
佘楚云 深圳供电局有限公司 
姚晓哲 深圳供电局有限公司 
周勇* 中国科学技术大学火灾安全全国重点实验室 230026
朱思宇 中国科学技术大学火灾安全全国重点实验室 
中文关键词:  变压器绝缘油  贫氧环境  电弧放电  爆炸极限  气体比值诊断
英文关键词:transformer insulating oil  oxygen-deficient environment  arc discharge  explosion limits  gas ratio diagnosis
摘要点击次数: 352
全文下载次数: 0
中文摘要:
      变压器少油设备在运行过程中内部易形成相对封闭的贫氧环境,当发生电弧放电时,绝缘油在高温高能作用下会发生热裂解,生成具有爆炸危险的可燃混合气体。为评估贫氧条件下电弧作用对变压器绝缘油产气及燃爆风险的影响,本文设计了密闭贫氧电弧实验装置,采用傅里叶变换红外光谱法,对不同电弧能量、油温及老化程度下的产气速率、气体组成及爆炸极限进行了研究。结果表明:油温由45 ℃升至90 ℃时,产气速率提高约一个数量级,最高达23.53 mL/s;随电弧能量由6 J增至13.8 J,混合气的爆炸下限由约3.3 %降至约2.8 %,爆炸上限由约16 %升至约32 %,可燃浓度区间显著扩大;老化144 h的油样产气速率和爆炸敏感性均达到峰值,288 h后略有回落,表现出中期劣化阶段燃爆敏感性最为突出的特征。在此基础上,本文引入乙炔体积分数及C?H?/C?H?、C?H?/C?H?比值,构建了不依赖氢气测量的改良三比值诊断思路,实现了贫氧环境下电弧放电能量等级与油质老化程度的区分。研究结果可为少油变压器及高压套管的电弧故障识别与防火防爆设计提供参考。
英文摘要:
      Reduced-oil transformer equipment tends to operate in a relatively enclosed, oxygen-deficient environment, in which an arc discharge can cause insulating oil to undergo thermal cracking under high temperature and high energy, generating combustible gas mixtures with explosion risk. To evaluate the gas generation and explosion risk under oxygen-deficient conditions, a sealed arc-discharge experimental setup was designed. Fourier-transform infrared (FTIR) spectroscopy was employed to investigate the gas generation rate, gas composition and theoretical explosion limits (LEL/UEL) under different arc energies, oil temperatures and ageing degrees. The results show that when the oil temperature increases from 45 °C to 90 °C, the gas generation rate rises by approximately one order of magnitude, with a maximum value of 23.53 mL/s. As the arc energy increases from 6 J to 13.8 J, the lower explosion limit decreases from about 3.3% to about 2.8%, while the upper explosion limit increases from about 16% to about 32%, indicating a significant expansion of the flammable concentration range. Oil aged for 144 h exhibits the highest gas generation rate and explosion sensitivity, which slightly decrease after 288 h. In addition, an improved three-ratio diagnostic scheme independent of hydrogen measurement is proposed using the acetylene volume fraction and the ratios C?H?/C?H? and C?H?/C?H?, enabling discrimination of arc energy levels and oil ageing degrees under oxygen-deficient conditions. The results can provide a useful reference for arc fault identification and fire and explosion prevention design of reduced-oil transformers and high-voltage bushings.